Standard functions
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
10-5
Te s t i n g
Testing can be carried out as follows:
• Via the "TEST/RESET" button on the basic unit and on the operator panel (can
be deactivated), as well as via PC with SIMOCODE ES software.
• Via the plugs of the internal "Test 1" or "Test 2" function blocks
• Via the menu of the operator panel with display (e.g. the "Commands" menu
item).
Testing can be terminated at any time - it does not influence the thermal
motor model of the overload function, i.e. after switching off via test, the
system can be reset immediately.
Tripping only occurs for Test 1 when the operating mode is set to "Remote".
Reset function
Resetting can be carried out as follows:
• Via the "TEST/RESET" button on the basic unit and on the operator panel (can
be deactivated), as well as via PC with SIMOCODE ES software.
• Using the "Reset input" plug of the internal function blocks via the plugs of
the internal function blocks "Reset 1", "Reset 2" and "Reset 3".
• Via the menu of the operator panel with display (e.g. the "Commands" menu
item).
The "Reset" function block consists of one plug.
Overall,
three function blocks, "Reset 1" through to "Reset 3" are available for
BU1 and BU2.
All reset inputs (sockets) are equal (OR function).
Te s t f u n c t i o n
A SIMOCODE pro function test can also be initialized via the test function.
The test function comprises the following steps:
• Lamp/LED test (test function < 2 s activated)
• Testing the device functionality (test function activated for 2 s - 5 s )
• For the "Test 1" function block only: Switching off the QE (test function
activated for > 5 s).