Standard functions
SIMOCODE pro
GWA 4NEB 631 6050-22 DS 03
10-23
"Safe tripping" response 1)
Here, you set the SIMOCODE pro response to a safety-oriented tripping via
DM-F Local or DM-F PROFIsafe.
Note:
The module response is not affected by this setting. In the event of the
conditions for safety-oriented tripping being fulfilled, the enabling circuits
are always opened!
Table 10-14: "Safe tripping" response
1) Note:
In the event that the option "DM-F LOCAL/PROFIsafe - separate function
from control function” has been activated under "Motor control > Control
function > Operating mode", "Tripping" can no longer be set as response;
"Deactivated", "Signaling" or "Warning" are the only remaining options.
"Safe tripping" reset
Here, you can select manual or automatic acknowledging of SIMOCODE pro
faults caused by safety-oriented tripping (default: manual).
Response Safe tripping
Tripping X
Deactivated X
Signaling X
Warning X
Reset: Manual
, Auto