Operating modes for calculator 2
The mode of the "Calculator 2" logic module can be changed via the
"Operating mode" parameter:
• Operating mode 1
The analog value at input 1 is combined with the analog value at input 2 via a
pre-defined formula, using the specified parameters (counters, denominators,
offsets, operators).
The result is available as an analog value at the output of the function block
for further processing (1 word/2 bytes).
• Operating mode 2
The analog values at input 1 and input 2 are processed together as a double
word. Input 1 represents the high word and input 2 the low word. The result
is calculated using the formula defined for this operating mode and using the
specified parameters (counters, denominators, offsets) and is output from
the function block as 1 word/2 bytes. In operating mode 2 it is also possible
to process double words (e.g. active power, apparent power) and to generate