Alarms, faults and system events
SIMOCODE pro
15-8 GWA 4NEB 631 6050-22 DS 03
Status - DM-F
enabling circuit
Shows the status of the
enabling circuit:
•closed
or
tripped
Status -
Emergency start
executed
The thermal memory has been
deleted with the function
"Emergency start".
The motor can be
switched on again
immediately after an
overload trip.
Status - Test
position (TPF)
The motor feeder is in the test
position (TPF).
The main current circuit has
been interrupted and "cold
starting" of the feeder can be
carried out.
17
Temperature
module -
Warning level
exceeded
The temperature warning level
has been exceeded.
Check the temperature
measuring station.
35
Temperature
module out of
range
Temperature sensor is delivering
impermissible values.
Check the temperature
sensor.
Reset Tripped 37
Temperature
module sensor
fault
Either a short circuit or an open
circuit has occurred in the
temperature sensor circuit.
Check the temperature
sensor and the sensor
cable.
Rectify the
fault; reset
Tripped 36
Test position
feedback (TPF)
Current is flowing in the motor
feeder although the motor
feeder is in the test position
(TPF).
The main circuit is not
interrupted in test
operation.
Reset or
OFF
command
Tripped
Test trip The motor feeder has been
checked and switched off by a
test trip.
Reset Tripped 65
Thermistor open
circuit
An open circuit has occurred in
the thermistor sensor cable.
Check the thermistor
sensor cable and the
thermistor.
Rectify the
fault; reset
Tripped 33
Thermistor short
circuit
A short circuit has occurred in
the thermistor sensor cable.
Check the thermistor
sensor cable and the
thermistor.
Rectify the
fault; reset
Tripped 32
Thermistor trip
level
Thermistor protection response.
The temperature of the motor is
too high.
Please check the motor
and the application that
is being driven by the
motor.
The motor cannot be
switched on again until
the temperature has
reached the switch-back
point of the thermistor.
Reset, auto-
reset
Tripped 31
Trip antivalence The limit switches are not
reporting any antivalent signals.
Limit switch open
circuit
Please check the
pos
itioner
application
and the limit switches
Counter
command
"OPEN/
CLOSED"
Tripped 16
Event
(alphabetical)
Description Troubleshooting Acknowledg
ement/fault
rectification
Contactor
control
Error
no.*)
Table 15-1: Alarms, faults and system events (Cont.)

Table of Contents

Other manuals for Siemens SIMOCODE pro

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMOCODE pro and is the answer not in the manual?

Siemens SIMOCODE pro Specifications

General IconGeneral
Protection ClassIP20
Mounting TypeDIN rail mounting
Rated Operational Voltage24 V DC
Rated CurrentUp to 820 A
Protection FunctionsOverload, short-circuit, phase failure, asymmetry, ground fault, motor stall
Operating Temperature Range-25°C to +60°C
Communication ProtocolsPROFIBUS DP, PROFINET, Modbus RTU
Analog OutputsUp to 2
Temperature MonitoringPTC/KTY, RTD (PT100/PT1000)
Digital OutputsRelay outputs, Solid-state outputs
Analog Inputs0/4-20mA, PT100/PT1000

Related product manuals