Additional system components
9.2 DRIVE-CLiQ Hub Module DMC20
SINAMICS S120 Combi
212 Manual, 11/2017, 6SL3097-4AV00-0BP7
9.2.3.2
X500-X505 DRIVE-CLiQ interfaces
Table 9- 16 X500-X505: DRIVE-CLiQ interfaces
Pin
Signal name
Technical data
1
TXP
Transmit data +
2
TXN
Transmit data -
3
RXP
Receive data +
4 Reserved, do not use
5
Reserved, do not use
6
RXN
Receive data -
7
Reserved, do not use
8
Reserved, do not use
A
+ (24 V)
Power supply
B
M (0 V)
Electronics ground
Connector type
DRIVE-CLiQ socket
The blanking covers for the DRIVE
-CLiQ interfaces are included in the scope of delivery.
Blanking covers (50 x) Article No.: 6SL3066-4CA00-0AA0
Note
Only MOTION
-CONNECT DRIVE-CLiQ cables may be used to establish connections.
The maximum length of MOTION
-CONNECT 500 is 100 m and for MOTION-CONNECT
800PLUS cables, 75
m.
9.2.3.3
X524 Electronics power supply
Table 9- 17 X524: Electronics power supply
Terminal
Designation
Technical specifications
+ Electronics power supply Voltage: 24 VDC (20.4 ... 28.8 V)
Current consumption: Maximum 0.5 A
Maximum current through the jumper in the
connector: 20 A (15 A according to UL/CSA)
+
Electronics power supply
M Electronics ground
M Electronics ground
Type: Screw terminal 3 (Page 288)
The maximum cable length that can be connected is 30 m.
Note
The two "+" and "M" terminals are jumpered in the connecto
r. This ensures that the supply
voltage is looped through.
The current consumption increases by the value for the DRIVE
-CLiQ participants.