Example for dimensioning a power cable 
Boundary conditions
: 
Module: S120 Combi 4 axes Power Module with 20 kW infeed 
Rated input current at 400 V
AC
: 34 A (from the technical data) 
Ambient temperature: 45° C 
Laying method: B2 
: 
With laying method B2 and a rated input current of 34 A
AC
, from the table showing the 
current-carrying capacity, a cable cross-section of 10 mm
2
 is obtained. 
 With a derating factor of 0.91 for 45° C ambient temperature, the current-carrying capacity of 
the selected power cable decreases to 36.4 A. 
: 
Under the given boundary conditions, a power cable with a cross-section of 10 mm
2
 can be 
used. 
 