Cabinet design and EMC 
  12.5 Connection system 
SINAMICS S120 Combi 
Manual, 11/2017, 6SL3097-4AV00-0BP7 
287 
 
Current-carrying capacity and derating factors for power cables and signal 
cables 
The current-carrying capacity of PVC/PUR-insulated copper cables is specified for laying 
methods B1, B2 and C under continuous operating conditions in the table with reference to 
an ambient air temperature of 40° C. For other ambient temperatures, the values must be 
corrected by the factors listed in the "Derating factors for deviating conditions" table. 
Table 12- 9  Current-carrying capacity according to EN 60204-1 for 40° C ambient temperature 
Effective current-carrying capacity; AC 50/60 Hz or DC  
for laying method 
0.50  –  7.5  7.5 
 
B1 cables in conduits or installation ducts
 
-core cables in conduits or installation ducts 
C cables along walls/panels without conduits and installation ducts 
 
Table 12- 10  Derating factors for deviating conditions 
Ambient temperature [° C] 
Derating factor according to EN 60204-1 Table D1