Cabinet design and EMC
12.8 Note on control cabinet cooling
SINAMICS S120 Combi
300 Manual, 11/2017, 6SL3097-4AV00-0BP7
Power loss of components in rated operation
12.8.4.1
The tables below provide an overview of the power loss of all components during rated
operation. The characteristic values apply for the following conditions:
● Line supply voltage 400 V
● Pulse frequency of the Motor Modules 4 kHz (clock frequency of the spindle 4 kHz or 8
kHz)
● Operating components at their rated power
The total losses of the relevant components (S120 Combi, Motor Module) are calculated
from the power loss and the corresponding losses from the electronics.
Power losses for SINUMERIK control systems, DC link components and
supplementary system components
Table 12- 17 Overview of power losses at rated operation for SINUMERIK control systems, DC link
components and supplementary system components
SINUMERIK NCU 710.3 PN W 21
Control Supply Module
Line
W
70