S120 Combi Power Modules
4.7 Installation
SINAMICS S120 Combi
Manual, 11/2017, 6SL3097-4AV00-0BP7
97
4.7.5
Mounting an external fan module
4.7.5.1
Description
The S120 Combi provides an integrated fan control and supply for an external 24 V fan unit.
The fan unit is connected via interface X12/X13. The outputs are designed for a maximum
total current of 2 A and are short-circuit and ground-fault proof.
The following functions are available when using the external fan unit:
Operating hours counter (see SINAMICS S120/S150 List Manual)
Setting the maximum operating time (see SINAMICS S120/S150 List Manual)
Evaluating fault signals
4.7.5.2
Overview
The external fan unit comprises the following components:
Fan cradle with seal for installation in the control cabinet
Connection cables with 4-pin connector
Double fan
Fan support plate
Air baffle plate