Line-side power components
3.8 Line connection versions
SINAMICS S120 Combi
Manual, 11/2017, 6SL3097-4AV00-0BP7
57
An isolating transformer must have the following properties:
The transformer secondary must be in the star connection (a delta connection is not
permissible!).
The neutral conductor must be brought out. It must be connected with the PE of the line
filter, line reactor and S120 Combi (infeed).
Comment
: If the neutral conductor is not brought out and/or not connected, then all of the
restrictions of an IT line supply apply!
Figure 3-11 Operation via an isolation transformer