No signals are preset for other traces you create for an S200 drive. Up to eight signals can be
selected.
• P
ossible cycle times:
In the "Cycle" input eld of the trace conguration, you can enter the cycle time with which
the trace should be recorded. The minimum cycle time for an S200 drive is 0.125ms.
• Selecting signal bits based on plain text descriptions:
By selecting a trigger variable, you can display individual signal bits based on plain text
descriptions (e.g. "Drive control.control wordsequence control.ON/OFF1") in the trace
conguration and select them directly. A description of how you can select an individual
signal bit and set a trigger event is provided below using the "Drive control.control
wordsequence control" trigger variable as an example.
More information
More information about the trace function and conguration in the TIAPortal, see TIAPortal
information system.
Example
In the following application, you want to make the basic settings for evaluating a trace.
1. Dene a trigger mode (e.g. "Trigger on tag") via the "Trigger mode" drop-down list.
2. To open the signal selection table, click the
in the "Trigger tag" input eld.
The signal selection table is display
ed.
3. In the signal selection table, scroll to the desired signal (e.g. "control word sequence control").
4. Click
in the row with the desired signal to open the bit selection table.
The bit selection table show
s the bits of the selected signal in plain text (e.g. "control
wordsequence control.ON/OFF1").
5. Select the required bit.
The selected bit is display
ed in "①".
Commissioning (Startdrive)
8.10Checking using the trace function
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 313