Acknowledgment: NONE
Explanation of the
mes
sage v
alue:
For %1
î™ Component in target topology
Explanation of the
mes
sage v
alue:
For %2, %3
î™
Value Cause Remedy
0 Component unknown î™
1 Control Unit î™
2 Motor Module î™
3 Line Module î™
4 Sensor Module î™
5 Voltage Sensing Module î™
6 Terminal Module î™
7 DRIVE-CLiQ Hub Module î™
8 Controller Extension î™
9 Filter module î™
10 Hydraulic Module î™
49 DRIVE-CLiQ component î™
50 Option slot î™
60 Encoder î™
70 DRIVE-CLiQ motor î™
71 Hydraulic cylinder î™
72 Hydraulic valve î™
80 Motor î™
Explanation of the
mes
sag
e v
alue:
For %4
î™
Value Cause Remedy
1 Di󹪜erent component type î™
2 Di󹪜erent article number î™
3 Di󹪜erent manufacturer î™
4 Incor
rect subcomponent connected î™
5 NX10 or NX15 used instead of CX32. î™
6 CX32 used instead of NX10 or NX15. î™
7 Di󹪜erent number of connections î™
Cause: The topology comparison has detected di󹪜er
ences in t
he actual and t
arget topologies in the electronic nameplate
component.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex:
aa = component number (%1),
bb = component class of the target topology (%2),
cc = component class of the actual topology (%3),
dd = di󹪜erence (%4)
Note:
The component class is described in F01375.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.