Acknowledgment: IMMEDIATELY
Cause: The actual checksum calculated by the drive and entered in r10098 via the safety-relevant parameters does not match the
r
efer
ence checksum saved in p10099 at the last machine acceptance.
Safety-relevant parameters have been changed or a fault is present.
Note:
This message results in an STO (Safe Torque O).
Message value (r60049, only for internal Siemens diagnostics)
Remedy: - Carry out safety commissioning.
- Carry out an accep
tance test.
C01677 SI: Incorrect onboard F-I/O parameter value
Message class: Error in the parameterization / conguration / commissioning pr
ocedure (18)
Message value: Parameter: %1, supplementary information: %2
Variant: S200 PN
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The parameter cannot be parameterized with this value.
No
te:
This mes
sage does not result in a safety stop response.
Message value (r60049, interpret decimal): yyyyxxxx dec:
yyyy = supplementary information
xxxx = parameter
yyyy = 0:
No additional information available.
xxxx = 10000 and
yyyy = F-DI number:
A non-existent F-DI was enabled.
xxxx = 10002:
The F-DI discrepancy time (p10002) is less than or equal to the SI monitoring clock cycle.
xxxx = 10017 and
yyyy = F-DI number:
The input lter (p10017) is less than or equal to (p10018 + 2ms) when simultaneously selecting "Self test using specied
dark pulses" (p10041[y] = 1).
xxxx = 10018 and
yyyy = F-DI number:
Setting "F-DI self test length dark pulses" (p10018) is zero when simultaneously selecting "Self test using specied dark
pulses" (p10041[y] = 1).
xxxx = 10041 and
yyyy = F-DI number:
An invalid value was set in "F-DI self test mode selection" (p10041[y]).
xxxx = 10071 and
yyyy = F-DI number:
An F-DI status r10071[y], which was not enabled in p10000, was set.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2