Remedy: Enter an existing time slice clock cycle. The fastest cycle time can be read out using the commissioning tool.
Note:
The alarm is r
eset as follows:
- Remove the cause of this alarm.
- Restart the function generator.
A02050 Trace: Start not possible
Message class: Error in the parameterization / conguration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The trace has already been started.
Remedy: Stop the trace and, if necessary, start again.
A02051 Trace: recording not possible as a result of know-how protection
Message class: Error in the parameterization / conguration / commissioning pr
ocedure (18)
Message value: initiating recorder: %1, parameter %2
Component: None
Response: NONE
Acknowledgment: NONE
Explanation of the
mes
sage v
alue:
For %1
Value Cause Remedy
1 Recorder 0
2 Recorder 1
3 Recorders 0 and 1
Cause: TRACE recording is not possible as at least one signal or trigger signal being used is under know-how protection.
Alarm v
alue (r2124, interpr
et hexadecimal):
bbbbaaaa hex:
aaaa = 1: recorder 0
aaaa = 2: recorder 1
aaaa = 3: recorders 0 and 1
bbbb = parameter number (hexadecimal), that was not able to be written to.
Remedy: - Temporarily activate or deactivate know-how protection (p7766).
- Include the signal in the OEM e
xception list (p7763, p7764).
- Where relevant do not record the signal.
A02055 Trace: Recording time too short
Message class: Error in the parameterization / conguration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The trace duration is too short.
The minimum is twice t
he value of t
he trace clock cycle.
Remedy: Check the selected recording time and, if necessary, adjust.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
494 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB