Cause: - A trigger signal was not specied.
- The specied signal does not exis
t.
- The specied signal is not a xed-point signal.
- The specied signal cannot be used as a trigger signal for the trace.
Remedy: Specify a valid trigger signal.
A02063 Trace: Invalid data type
Message class: Error in the parameterization / conguration / commissioning procedure (18)
Message value: %1
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The specied dat
a type to select a signal using a ph
ysical address is invalid.
Remedy: Use a valid data type.
A02070 Trace: Parameter cannot be changed
Message class: Error in the parameterization / conguration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The trace parameter settings cannot be changed when the trace is active.
Remedy: - Stop the trace before parameterization.
- If r
equir
ed, start the trace.
A02075 Trace: Pretrigger time too long
Message class: Error in the parameterization / conguration / commissioning procedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The selected pretrigger time must be shorter than the trace time.
Remedy: Check the pretrigger time setting and change if necessary.
F02080 Trace: Parameterization deleted due to unit changeover
Message class: Error in the parameterization / conguration / commissioning pr
ocedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The trace parameterization in the drive unit was deleted due to a unit changeover or a change in the reference parameters.
Remedy: Restart trace.
A02085 Message function: Parameterization error
Message class: Error in the parameterization / conguration / commissioning pr
ocedure (18)
Message value: Parameter: %1, index:%2
Component: Power Unit
Response: NONE
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
496 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB