A02099 Trace: Insu󹪟cient Control Unit memor
y
Message class: Error in the parameterization / con󹪝guration / commissioning procedure (18)
Message value: -
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The memory space still available on the Control Unit is no longer su󹪟cient f
or the tr
ace function.
Remedy: Reduce the memory required, e.g. as follows:
- Reduce the trace time.
- Incr
ease the trace clock cycle.
- Reduce the number of signals to be traced.
A02150 TEC: Technology Extension cannot be loaded
Message class: Hardware/software error (1)
Message value: %1
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The system was not able to load a Technology Extension.
Alarm v
alue (r2124, interpr
et hexadecimal):
10 hex (16 dec):
The interface version in the DCB user library is not compatible to the DCC standard library that has been loaded.
12 hex (18 dec):
A technology package was not able to be downloaded to a Control Unit because the warm restart necessary was not able
to be performed.
Only for internal Siemens troubleshooting.
Remedy: - Carry out a POWER ON (switch-o󹪜/switch-on) f
or all components.
- Upgrade 󹪝rmware to later version.
- Contact Technical Support.
For alarm value = 10 hex (16 dec):
Load a compatible DCB user library (compatible to the interface of the DCC standard library).
For alarm value = 12 hex (18 dec):
Carry out a POWER ON (switch-o󹪜/switch-on) for all components.
Note:
DCB: Drive Control Block
DCC: Drive Control Chart
TEC: Technology Extension
F02151 TEC: internal software error
Message class: Hardware/software error (1)
Message value: %1
Component: None
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: An internal software error has occurred within a Technology Extension.
F
ault value (r0949, interpret hexadecimal):
Only for internal Siemens troubleshooting.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
498 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB