Remedy: - Carry out a POWER ON (switch-o/switch-on) f
or all components.
- Upgrade rmware to later version.
- Contact Technical Support.
- Replace the Control Unit.
Note:
TEC: Technology Extension
F02152 TEC: insucient memory
Messag
e class: Hardware/software error (1)
Message value: %1
Component: None
Response: OFF1
Acknowledgment: IMMEDIATELY
Cause: The functionality on this Control Unit is too extensive (e.g. too many drives, functions, data sets, Technology Extensions,
bloc
ks, e
tc).
Fault value (r0949, interpret decimal):
Only for internal Siemens troubleshooting.
Remedy: - Change the conguration on this Contr
ol Unit, e.g.
-- Use fewer axes
-- Reduce the number of congurable functions
-- Use fewer data sets
-- Reduce Technology Extensions and blocks
- Use an additional Control Unit.
F02153 TEC: technology function does not exist
Message class: Hardware/software error (1)
Message value: -
Component: None
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: A technology function (e.g. Technology Extension, DCB library) does not exist on the drive device.
When congur
ing, a tec
hnology function is activated, which does not exist on the drive device. This can occur when
downloading a project or when powering up.
Remedy: - Load the required technology function to the drive device.
- If requir
ed, deactivate the technology function not required in the conguration.
Note:
DCB: Drive Control Block
TEC: Technology Extension
F03001 NVRAM checksum incorrect
Message class: Hardware/software error (1)
Message value: %1
Component: Control Unit (CU)
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: A checksum error occurred when evaluating the non-volatile data (NVRAM) on the converter.
The NVRAM dat
a aect
ed was deleted.
Remedy: Carry out a POWER ON (switch-o/switch-on) f
or all components.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 499