A03506 24 V power supply missing
Message class: Supply voltage fault (undervoltage) (3)
Message value: %1
Component: None
Response: NONE
Acknowledgment: NONE
Cause: The 24 V power supply for the digital outputs (X124) is missing.
Remedy: Check the terminals for the power supply voltage (X124, L1+, M).
F03590 TM: Module not ready
Message class: Error in the parameterization / con󹪝gur
ation / commis
sioning pr
ocedure (18)
Message value: %1
Component: Terminal Module (TM)
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The Terminal Module involved does not send a ready signal and no valid cyclic data.
F
ault value (r0949, int
erpret decimal):
Drive object number of the Terminal Module involved.
Remedy: - Check the 24 V power supply.
- Check the DRIVE-CLiQ wir
ing.
F05055 Parallel connection: Power units with illegal code numbers
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: Parameter: %1
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The code numbers of the power units do not match.
F
ault value (r0949, int
erpret decimal):
Parameter in which the 󹪝rst di󹪜erent power unit code number was detected.
Remedy: Use power units with the same code number.
For parallel cir
cuit con󹪝gurations, only power units with identical power unit data may be used.
F05056 Parallel circuit: Power unit EEPROM versions di󹪜er
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: Parameter: %1
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The EEPROM versions of the power units do not match.
F
ault value (r0949, int
erpret decimal):
Parameter in which the 󹪝rst di󹪜erent version number was detected.
Remedy: Use power units with the same EEPROM version.
Note:
F
or parallel circuit con󹪝gurations, only power units with identical EEPROM versions may be used.
F05057 Parallel circuit: Power unit 󹪝rmwar
e versions di󹪜er
Message class: Error in the parameterization / con󹪝guration / commissioning pr
ocedure (18)
Message value: Parameter: %1
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
500 Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB