Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: The 󹪝rm
ware ver
sions of the power units connected in parallel do not match.
Fault value (r0949, interpret decimal):
Parameter in which the 󹪝rst di󹪜erent version number was detected.
Remedy: Use power units with the same 󹪝rmwar
e version.
For parallel circuit con󹪝gurations, only power units with identical 󹪝rmware versions may be used.
F05058 Parallel circuit: VSM EEPROM versions di󹪜er
Message class: General drive fault (19)
Message value: Parameter: %1
Component: Voltage Sensing Module (VSM)
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The EEPROM versions of the Voltage Sensing Modules (VSM) do not match.
F
ault v
alue (r0949, int
erpret decimal):
Parameter in which the 󹪝rst di󹪜erent version number was detected.
Remedy: For parallel circuit con󹪝gurations, only V
oltage Sensing Modules (VSM) with identical EEPROM versions may be used.
F05059 Parallel circuit: VSM 󹪝rmwar
e versions di󹪜er
Message class: General drive fault (19)
Message value: Parameter: %1
Component: Voltage Sensing Module (VSM)
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The 󹪝rm
ware ver
sions of the Voltage Sensing Module (VSM) do not match.
Fault value (r0949, interpret decimal):
Parameter in which the 󹪝rst di󹪜erent version number was detected.
Remedy: For parallel circuit con󹪝gurations, only V
oltage Sensing Modules (VSM) with identical 󹪝rmware versions may be used.
F05060 Parallel circuit: Power unit 󹪝rmware version does not match
Message class: Error in the parameterization / con󹪝guration / commissioning procedure (18)
Message value: Parameter: %1
Component: Power Unit
Response: OFF2
Acknowledgment: IMMEDIATELY
Cause: Firmware from version V02.30.01.00 is required when connecting the power units in parallel.
Remedy: Update the 󹪝rm
war
e of the power units (at least V02.30.01.00).
F05068 Parallel connection: AIM EEPROM versions di󹪜erent
Message class: General drive fault (19)
Message value: Parameter: %1
Component: -
Response: NONE
Acknowledgment: IMMEDIATELY
Cause: The EEPROM versions of the Active Interface Module (AIM) do not match.
F
ault value (r0949, int
erpret decimal):
Parameter in which the 󹪝rst di󹪜erent version number was detected.
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 501