Remedy: - Reduce the motor load.
- Check the ambient t
emperature and the motor ventilation.
- Check the wiring and temperature sensor connection.
- Check monitoring limits.
- Check activation of the additional motor overload protection (5375).
A07012 Drive: Motor temperature model overtemperature
Message class: Motor overload (8)
Message value: %1
Component: Motor
Response: NONE
Acknowledgment: NONE
Cause: Motor temperature model 1/3 or the additional motor overload protection identied
t
hat
the alarm threshold was exceeded.
Hysteresis:2K
Alarm value (r2124, interpret decimal):
200:
Motor temperature model 1 (I2t): temperature too high.
300:
Motor temperature model 3: temperature too high.
400:
Additional motor overload protection: the load is too high. If the load remains at this level, the drive is shut down with fault
F07011.
See also: r0034, p0613
Remedy: - Check the motor load and if required, reduce.
- Check the mo
tor ambient temperature.
- Check activation of the additional motor overload protection (p5375).
See also: r0034 (Motor utilization thermal)
F07082 Macro: Execution not possible
Message class: Error in the parameterization / conguration / commissioning pr
ocedure (18)
Message value: Fault cause: %1, supplementary information: %2, preliminary parameter number: %3
Component: None
Response: NONE
Acknowledgment: IMMEDIATELY
System messages
12.3Faults and alarms
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2