Note
Modi󹪝ed parame
ters are displayed in indices 0 to 298. If an index contains the value 0, then the list ends here. In a long
list, index 299 contains the parameter number at which position the list continues.
This list consists solely of the following parameters:
r0980[0...299], r0981[0...299] ... r0989[0...299]
The parameters in this list are not displayed in the parameter lists of the commissioning tool. However, they can be read
from a higher-level control system (e.g. PROFIBUS master).
p1082[0] Maximum speed
Data type: FloatingPoint32 Visible in: S
tandard display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or driv
e applications
Can be changed in the operating
stat
e:
Ready for operation
Parameter group: Motorized potentiometer, Speed limiting, U/f control, Speed controller, Quick
commissioning
Unit
: rpm
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
1500.000 [rpm]
Description: Sets the maximum motor speed to a value less than or equal to the maximum motor speed (p0322).
The set value is v
alid for both directions of rotation.
Dependency: See also: p0322
p1083[0] Speed limit in positive direction of rotation
Data type: FloatingPoint32 Visible in: S
tandard display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or driv
e applications
Can be changed in the operating
stat
e:
Operation
Parameter group: Speed limiting, U/f control, Speed controller
Unit: rpm
Min:
0.000 [rpm]
Max:
210000.000 [rpm]
Factory setting:
210000.000 [rpm]
Description: Sets the maximum speed for the positive direction.
p1086[0] Speed limit in negative direction of rotation
Data type: FloatingPoint32 Visible in: S
tandard display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or driv
e applications
Can be changed in the operating
stat
e:
Operation
Parameter group: Speed limiting, U/f control, Speed controller
Unit: rpm
Min:
-210000.000 [rpm]
Max:
0.000 [rpm]
Factory setting:
-210000.000 [rpm]
Description: Sets the speed limit for the negative direction.
Appendix
A.3Parameters
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 733