p5309[0] One Button Tuning test signal duration
Data type: Unsigned32 Visible in: S
tandard display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device congur
ation or driv
e applications
Can be changed in the operating
stat
e:
Ready for operation
Parameter group:
Unit: ms
Min:
0 [ms]
Max:
5000 [ms]
Factory setting:
2000 [ms]
Description: Sets the test signal sequence duration (several acceleration operations).
This function is used for One Button T
uning (p5300 = 1) to identify the total moment of inertia of the drive train.
Dependency: See also: F07093
p5375[0].0...1 Additional motor overload protection conguration
Data type: Unsigned16 Visible in: Ext
ended display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device congur
ation or driv
e applications
Can be changed in the operating
stat
e:
Operation
Parameter group: Motor temperature
Unit: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description: Sets the conguration for additional mo
tor overload protection.
Bit array: Bit Signal name 1 signal 0 signal
00 Activate monitoring Yes No
01 Activation of speed dependency Yes No
Note
T
o compl
y with standard UL 61800-5-1 Ed. 2, bit 0 and bit 1 must be set.
These bits activate electronic motor overload protection according to IEC 61800-5-1 Ed. 3 / UL 61800-5-1 Ed. 2, with the
emulation of an electronic overload relay, Class 20 and the speed sensitivity.
For bit 00:
This bit activates electronic motor overload protection with emulation of an electronic overload relay, Class 20.
For bit 01:
This bit activates the speed dependency of the electronic motor overload protection. Not active, if bit 00 is also set.
r8400[0...2] Date
Data type: Unsigned16 Visible in: S
tandard display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device congur
ation or driv
e applications
Parameter group: Diagnostics general
Unit: -
Description: Displays the actual date in year, month and day.
Index: [0] = Year (YYYY)
[1] = Mont
h (1 ... 12)
[2] = Day (1 ... 31)
Appendix
A.3Parameters
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 849