r10080.0...7 SI status signals channel A
S200 PN Data type: Unsigned32 Visible in: Ext
ended display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or driv
e applications
Parameter group:
Unit: -
Description: Status signals (channel A) for safety-relevant motion monitoring functions integrated in the drive.
Bit array: Bit Signal name 1 signal 0 signal
00 STO or safe pulse cancellation active Yes No
07 Internal event No Yes
NOTICE
For bit 07:
An int
ernal ev
ent is displayed if STO is active.
r10098 SI actual checksum across device-speci󹪝c parame
ters
S200 PN Data type: Unsigned32 Visible in: Ext
ended display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or driv
e applications
Parameter group: Basic functions
Unit: -
Description: Displays the checksum over the checksum-checked parameters for the device-speci󹪝c par
ameters of the drive system
(actual checksum).
Dependency: See also: p10099
p10099 SI reference checksum across device-speci󹪝c parame
ters
S200 PN Data type: Unsigned32 Visible in: Ext
ended display
Read permission: Read drive data or acknowledge messages
Write permission: Edit Safety Integrated application
Can be changed in the operating
s
tat
e:
Commissioning (Safety Integrated)
Parameter group: Basic functions
Unit: -
Min:
0000 he
x
Max:
FFFF FFFF hex
Factory setting:
A1A1 A1A1 hex
Description: Displays the checksum over the checksum-checked parameters for the device-speci󹪝c par
ameters of the drive system
(reference checksum).
Dependency: See also: r10098
r10151.0 SI digital inputs status channel B
S200 PN Data type: Unsigned8 Visible in: Standard display
Read permission: Read drive data or acknowledge messages
Write permission: Edit device con󹪝gur
ation or driv
e applications
Parameter group:
Unit: -
Description: Display for the single-channel, logical and debounced status of the failsafe digital inputs of channel B.
Bit array: Bit Signal name 1 signal 0 signal
00 Status of DI 11+ (X131.5/6) Logical 1 Logical 0
Dependency: See also: p10017, p10040
Appendix
A.3Parameters
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB 867