Table 39: Torque reference parameters
Index Parameter Min Max Unit Default ID Description
P3.3.2.3
Torque Maximum
Reference
-300.0 300.0 % 100.0 642
The torque reference
that agrees to the
maximum value of the
reference signal. This
value is used as the
maximum torque
reference for negative
and positive values.
P3.3.2.4
Torque Reference
Filter Time
0.00 300.00 s 0.00 1244
Gives the filtering time
for the final torque
reference.
P3.3.2.5
Torque Reference
Dead Zone
0.0 300.0 % 0.0 1246
To ignore the small
values around 0 of the
torque reference, set
this value to be bigger
than 0. When the
reference signal is
between 0 and 0 ± the
value of this
parameter, the torque
reference is set to 0.
P3.3.2.6
Keypad Torque
Reference
0.0 P3.3.2.3 % 0.0 1439
Used when P3.3.2.1. is
set to 1. The value of
this parameter is
limited between
P3.3.2.3. and P3.3.2.2.
P3.3.2.7
Torque Control
Frequency Limit
0 1 0 1278
The selection of the
output frequency limit
mode for the torque
control.
0 = Pos/Neg frequency
limits
1 = frequency
reference
M3.3.2.8
Torque Control Open
Loop
This menu includes 3 parameter. See table below.
VACON · 128 PARAMETERS MENU
5