Table 83: Setpoint settings
Index Parameter Min Max Unit Default ID Description
P3.13.2.1 Keypad setpoint 1 Varies Varies Varies 0 167
P3.13.2.2 Keypad setpoint 2 Varies Varies Varies 0 168
P3.13.2.3 Setpoint ramp time 0.00 300.0 s 0.00 1068
Gives the rising and
falling ramp times for
the setpoint changes.
That is, the time to
change from the
minimum to the
maximum.
P3.13.2.4
PID setpoint boost
activation
Varies Varies
DigIN
Slot0.1
1046
FALSE = No boost
TRUE = Boost
P3.13.2.5 PID select setpoint Varies Varies
DigIN
Slot0.1
1047
FALSE = Setpoint 1
TRUE = Setpoint 2
VACON · 174 PARAMETERS MENU
5