Drive Model Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
4A1200
R/L1, S/L2, T/L3, R1/L11, S1/L21,
T1/L31
300 × 4P×2 4/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 × 4P×2 4/0 to 300
⊖, ⊕1
– 250 to 300
⊕3
– 4/0 to 300
4/0 4/0 to 250
<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.
<2>
Install a GFCI or use 10 mm
2
(AWG 8) copper wire when using this wire gauge in accordance with IEC/EN 61800-5-1.
Note: When connecting peripheral devices or options to terminals ⊖, ⊕1, ⊕3, B1, and B2, refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
n
Three-Phase 600 V Class
Table 3.5
Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
Drive Model Terminal
Recomm. Gauge
mm
2
(AWG, kcmil)
Wire Range
mm
2
(AWG, kcmil)
Screw
Size
Tightening Torque
N·m (lb.in.)
5A0003
5A0004
5A0006
R/L1, S/L2, T/L3
2.5
(14)
2.5 to 6.0
(14 to 10)
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
2.5
(14)
2.5 to 6.0
(14 to 10)
⊖, ⊕1, ⊕2
–
2.5 to 6.0
(14 to 10)
B1, B2 –
2.5 to 6.0
(14 to 10)
6.0
(10)
2.5 to 6.0
(14 to 10)
5A0009
R/L1, S/L2, T/L3
2.5
(14)
2.5 to 6.0
(14 to 10)
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3
2.5
(14)
2.5 to 6.0
(14 to 10)
⊖, ⊕1, ⊕2
–
2.5 to 6.0
(14 to 10)
B1, B2 –
2.5 to 6.0
(14 to 10)
6.0
(10)
4.0 to 6.0
(12 to 10)
5A0011
R/L1, S/L2, T/L3
6.0
(10)
2.5 to 16
(14 to 6)
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3
2.5
(14)
2.5 to 16
(14 to 6)
⊖, ⊕1, ⊕2
–
2.5 to 16
(14 to 6)
B1, B2 –
2.5 to 6.0
(14 to 10)
10
(8)
4.0 to 6.0
(12 to 8)
M5
2.0 to 2.5
(17.7 to 22.1)
5A0017
R/L1, S/L2, T/L3
6.0
(10)
6.0 to 16
(10 to 6)
M5
3.6 to 4.0
(31.8 to 35.4)
U/T1, V/T2, W/T3
6.0
(10)
6.0 to 16
(10 to 6)
⊖, ⊕1, ⊕2
–
6.0 to 16
(10 to 6)
B1, B2 –
6.0 to 10
(10 to 8)
2.7 to 3.0
(23.9 to 26.6)
10
(8)
6.0 to 10
(12 to 8)
M6
5.4 to 6.0
(47.8 to 53.1)
3.6 Main Circuit Wiring
100
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide