Three-Phase 600 V Class Drive Models 5A0125 to 5A0242
Table A.10 Power Ratings Continued (Three-Phase 600 V Class)
Item Specification
Drive Models 5A0125 5A0145 5A0192 5A0242
Maximum Applicable Motor Capacity (HP)
<1>
ND Rating 125 150 200 250
HD Rating 100 125 150 200
Input
Input Current (A)
<2>
ND Rating 129 158 228 263
HD Rating 108 129 158 228
Rated Voltage
Rated Frequency
Three-phase 500 to 600 Vac 50/60 Hz
Allowable Voltage Fluctuation -10 (-15) to +10%
Allowable Frequency Fluctuation ±5%
Input Power (kVA)
ND Rating 147 181 261 301
HD Rating 123 147 181 261
Output
Rated Output Capacity (kVA)
<3>
ND Rating
<4>
124 144 191 241
HD Rating
<4>
99 129 171 199
Rated Output Current (A)
ND Rating
<4>
125 145 192 242
HD Rating
<4>
99 130 172 200
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency User adjustable between 2 and 3kHz
Maximum Output Voltage (V) Three-phase 500 to 600 Vac (proportional to input voltage)
Maximum Output Frequency (Hz) 400 Hz (user-set)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2>
Assumes operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring
connections, and power supply impedance.
<3> Rated motor capacity is calculated with a rated output voltage of 575 V.
<4> Carrier frequency can be increased to 2 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<5> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<6> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
A.2 Power Ratings
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
243
A
Specifications

Table of Contents

Other manuals for YASKAWA A1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 Series and is the answer not in the manual?

YASKAWA A1000 Series Specifications

General IconGeneral
SeriesA1000
TypeAC Drive
AltitudeUp to 1000m without derating
Output Frequency0-400 Hz
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Communication OptionsModbus, DeviceNet, Profibus, Ethernet/IP
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Horsepower0.5 to 1000 HP
Power Range0.4 - 630 kW (varies by voltage and model)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Cooling MethodFan Cooled
SafetySafe Torque Off (STO)