B.9 n: Special Adjustment
The n parameters adjust more advanced performance characteristics such as Hunting Prevention, speed feedback detection,
High Slip Braking, and Online Tuning for motor line-to-line resistance.
u
n1: Hunting Prevention
No.
(Addr.
Hex)
Name LCD Display Description Values Page
n1-01
(0580)
Hunting Prevention
Selection
Hunt Prev Select
0: Disabled
1: Enabled
0: Disabled
1: Enabled
Default: 1
Range: 0, 1
n1-02
(0581)
Hunting Prevention Gain
Setting
Hunt Prev Gain
If the motor vibrates while lightly loaded, increase the gain by
0.1
until vibration ceases. If the motor stalls, decrease the gain
by 0.1 until the stalling ceases.
Default: 1.00
Min.: 0.00
Max.: 2.50
n1-03
(0582)
Hunting Prevention
Time Constant
Hunt Prev Time
Sets the time constant used for Hunting Prevention.
Default:
<1>
Min.: 0 ms
Max.: 500 ms
n1-05
(0530)
Hunting Prevention Gain
while in Reverse
Hprev Gain @Rev
Sets the gain used for Hunting Prevention. If set to 0, the gain
set to n1-02 is used for operation in reverse.
Default: 0.00
Min.: 0.00
Max.: 2.50
<1> Default setting is determined by parameter o2-04, Drive Model Selection.
u
n2: Speed Feedback Detection Control (AFR) Tuning
No.
(Addr.
Hex)
Name LCD Display Description Values Page
n2-01
(0584)
Speed Feedback
Detection
Control (AFR)
Gain
AFR Gain
Sets the internal speed feedback detection control gain in the
automatic frequency regulator (AFR).
If hunting occurs, increase the set value. If response is low,
decrease the set value.
Default: 1.00
Min.: 0.00
Max.: 10.00
n2-02
(0585)
Speed Feedback
Detection Control (AFR)
Time Constant 1
AFR Time
Sets the time constant used for speed feedback detection control
(AFR).
Default: 50 ms
Min.: 0
Max.: 2000
n2-03
(0586)
Speed Feedback
Detection Control (AFR)
Time Constant 2
AFR Time 2
Sets the AFR time constant to be used during Speed Search and
during regen.
Default: 750 ms
Min.: 0
Max.: 2000
u
n3: High Slip Braking (HSB) and Overexcitation Braking
No.
(Addr.
Hex)
Name LCD Display Description Values Page
n3-01
(0588)
High-Slip Braking
Deceleration Frequency
Width
HSB DecStepWidth
Sets the output frequency reduction step width for when the
drive stops the motor using HSB. Set as a percentage of the
maximum
output frequency. Increase this setting if overvoltage
occurs during HSB.
Default: 5%
Min.: 1
Max.: 20
n3-02
(0589)
High-Slip Braking
Current Limit
HSB Current Lim
Sets the current limit during HSB as a percentage of the motor
rated current.
Default:
<1>
Min.: 100%
Max.:
<1>
n3-03
(058A)
High-Slip Braking
Dwell Time at Stop
HSB DwelTim@Stp
Sets the time the drive will run with minimum frequency
(E1-09) at the end of deceleration.
If this time is set too low, the machine inertia can cause the
motor to rotate slightly after HSB.
Default: 1.0 s
Min.: 0.0
Max.: 10.0
n3-04
(058B)
High-Slip Braking
Overload Time
HSB OL Time
Sets the time required for an HSB overload fault (oL7) to occur
when the drive output frequency does not change during an
HSB stop. This parameter does not typically require
adjustment.
Default: 40 s
Min.: 30
Max.: 1200
n3-13
(0531)
Overexcitation
Deceleration Gain
Hflux Brake Gain
Sets the gain applied to the V/f pattern during Overexcitation
Deceleration (L3-04 = 4).
Default: 1.10
Min.: 1.00
Max.: 1.40
B.9 n: Special Adjustment
308
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide

Table of Contents

Other manuals for YASKAWA A1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 Series and is the answer not in the manual?

YASKAWA A1000 Series Specifications

General IconGeneral
SeriesA1000
TypeAC Drive
AltitudeUp to 1000m without derating
Output Frequency0-400 Hz
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Communication OptionsModbus, DeviceNet, Profibus, Ethernet/IP
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Horsepower0.5 to 1000 HP
Power Range0.4 - 630 kW (varies by voltage and model)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Cooling MethodFan Cooled
SafetySafe Torque Off (STO)