C.2 UL and CSA Standards
u
UL Standards Compliance
The UL/cUL mark applies to products in the United States and Canada. It indicates that UL has performed product testing and
evaluation, and determined that their stringent standards for product safety have been met. For a product to receive UL
certification, all components inside that product must also receive UL certification.
Figure C.7 UL/cUL Mark
This drive is tested in accordance with UL standard UL508C and complies with UL requirements. The conditions described
below must be met to maintain compliance when using this drive in combination with other equipment:
n
Installation Area
Do not install the drive to an area greater than pollution degree 2 (UL standard).
n
Ambient Temperature
IP00/Open Type Enclosure: -10 °C to +50 °C (14 °F to 122 °F)
IP20/UL Type 1 Enclosure: -10 to +40 °C (14 °F to 104 °F)
Finless Type: IP20/IP00 Enclosure: -10 to +45 °C (14 °F to 113 °F)
n
Main Circuit Terminal Wiring
Yaskawa recommends using closed-loop crimp terminals on all drive models. To maintain UL/cUL approval, UL Listed
closed-loop crimp terminals are specifically required when wiring the drive main circuit terminals on models 2A0110 to
2A0415, 4A0058 to 4A0675, (4A1200 series-dependent), and 5A0041 to 5A0242. Use only the tools recommended by the
terminal
manufacturer for crimping. Refer to Closed-Loop Crimp Terminal Recommendations on page 340 for closed-loop
crimp terminal recommendations.
Closed-Loop Crimp Terminal Recommendations
To maintain UL/cUL approval, UL Listed closed-loop crimp terminals are specifically required when wiring the drive main
circuit terminals on models 2A0110 to 2A0415, 4A0058 to 4A1200, and 5A0041 to 5A0242. Use only the tools recommended
by the terminal manufacturer for crimping. Yaskawa recommends UL Listed crimp terminals made by JST and Tokyo DIP
(or equivalent) for the insulation cap. Table C.6 matches the wire gauges and terminal screw sizes with Yaskawa-recommended
crimp terminals, tools, and insulation caps. Refer to the appropriate Wire Gauge and Torque Specifications table for the wire
gauge and screw size for your drive model. Place orders with a Yaskawa representative or the Yaskawa sales department.
Wire gauge values shown in bold italic are the recommended values. Refer to local codes for proper selections.
Table C.6 Closed-Loop Crimp Terminal Size
Drive Model
Wire Gauge (AWG, kcmil)
Screw
Size
Crimp
Terminal
Model
Number
Tool
Insulation
Cap Model
No.
Code
<1>
R/L1, S/L2, T/L3 U/T1, V/T2, W/T3 Machine No. Die Jaw
200 V Class
2A0004
2A0006
2A0008
2A0010
14
M4
R2-4
YA-4 AD-900
TP-003 100-054-028
12
R5.5-4 TP-005 100-054-029
10
2A0012
14 14
M4
R2-4
YA-4 AD-900
TP-003 100-054-028
12 12
R5.5-4 TP-005 100-054-029
10
C.2 UL and CSA Standards
340
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide

Table of Contents

Other manuals for YASKAWA A1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 Series and is the answer not in the manual?

YASKAWA A1000 Series Specifications

General IconGeneral
SeriesA1000
TypeAC Drive
AltitudeUp to 1000m without derating
Output Frequency0-400 Hz
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Communication OptionsModbus, DeviceNet, Profibus, Ethernet/IP
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Horsepower0.5 to 1000 HP
Power Range0.4 - 630 kW (varies by voltage and model)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Cooling MethodFan Cooled
SafetySafe Torque Off (STO)

Related product manuals