Three-Phase 400 V Class Drive Models 4A0038 to 4A0165
Table A.6 Power Ratings Continued (Three-Phase 400 V Class)
Item Specification
Drive Models 4A0038 4A0044 4A0058 4A0072 4A0088 4A0103 4A0139 4A0165
Maximum Applicable Motor
Capacity (HP)
<1>
ND Rating 25 30 40 50 60 75 100 125
HD Rating 20 25-30 25-30 40 50-60 50-60 75 100
Input
Input Current (A)
<2>
ND Rating 44 52 58 71 86 105 142 170
HD Rating 39 44 43 58 71 86 105 142
Rated Voltage
Rated Frequency
Three-phase: 380 to 480 Vac 50/60 Hz/510 to 680 Vdc
<3>
Allowable Voltage Fluctuation -15 to 10%
Allowable Frequency Fluctuation ±5%
Input Power (kVA)
ND Rating 40 48 53 65 79 96 130 155
HD Rating 36 40 39 53 65 79 96 130
Output
Rated Output Capacity
(kVA)
<4>
ND Rating
<5>
29 34 44 55 67 78 106 126
HD Rating 24 30 34 46 57 69
85
<7>
114
<7>
Rated Output Current
(A)
ND Rating
<5>
38 44 58 72 88 103 139 165
HD Rating
31
<6>
39
<6>
45
<6>
60
<6>
75
<6>
91
<6>
112
<7>
150
<7>
Overload Tolerance
ND Rating: 120% of rated output current for 60 s
HD Rating: 150% of rated output current for 60 s
(Derating may be required for applications that start and stop frequently)
Carrier Frequency User adjustable between 1 and 15 kHz
User adjustable
between 1 and
10 kHz
Maximum Output Voltage (V) Three-phase: 380 to 480 Vac (proportional to input voltage)
Maximum Output Frequency (Hz) 400 Hz (user-adjustable)
<1> The motor capacity (HP) refers to a NEC rated 4-pole motor. The rated output current of the drive output amps should be equal to or greater than
the motor current. Select the appropriate capacity drive if operating the motor continuously above motor nameplate current.
<2> Assumes
operation at the rated output current. Input current rating varies depending on the power supply transformer, input reactor, wiring conditions,
and power supply impedance.
<3> DC input is not available for UL standards.
<4> Rated motor capacity is calculated with a rated output voltage of 440 V.
<5> Carrier frequency is set to 2 kHz. Current derating is required in order to raise the carrier frequency.
<6> Carrier frequency can be increased to 8 kHz while keeping this current derating. Higher carrier frequency settings require derating.
<7> Carrier frequency can be increased to 5 kHz while keeping this current derating. Higher carrier frequency settings require derating.
A.2 Power Ratings
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide