Digital Operator Display Fault Name
oL3
Overtorque Detection 1
The current has exceeded the value set for Torque Detection Level 1 (L6-02) for longer than the allowable
time (L6-03).
Cause Possible Solution
Parameter settings are not appropriate for the
load
Check L6-02 and L6-03 settings.
Fault on the machine side (e.g., machine is
locked up)
Check the status of the load. Remove the cause of the fault.
oL4
Overtorque Detection 2
The current has exceeded the value set for Torque Detection Level 2 (L6-05) for longer than the allowable
time (L6-06).
oL5
Mechanical Weakening Detection 1
Overtorque occurred, matching the conditions specified in L6-08.
oL7
High Slip Braking oL
The output frequency stayed constant for longer than the time set to n3-04 during High Slip Braking.
Digital Operator Display Fault Name
oPr
External Digital Operator Connection Fault
The external operator has been disconnected from the drive.
Note: An oPr fault will occur when all of the following conditions are true:
Output is interrupted when the operator is disconnected (o2-06 = 1).
The Run command is assigned to the operator (b1-02 = 0 and LOCAL has been selected).
Cause Possible Solution
External operator is not properly connected to
the drive
Check the connection between the operator and the drive.
Replace the cable if damaged.
Turn off the drive input power and disconnect the operator. Reconnect the operator and reapply drive
input power.
oS
Overspeed
The motor speed feedback exceeded the F1-08 setting.
5.2 Fault Detection
190