C6-09
(022B)
Carrier Frequency
during Rotational Auto-
Tuning
Carrier in tune
0: Fc = 5kHz
1: Fc = C6-03
0: Carrier Frequency = 5 kHz. In PM control modes, this value
is 2 kHz.
1: Setting value for C6-03. In PM control modes, this value is
the carrier frequency set in C6-02.
Note: This parameter is not available in models
4A0930 and 4A1200.
Default: 0
Range: 0, 1
<1> Default
setting value is determined by parameters A1-02, Control Method Selection, C6-01, Drive Duty Selection, and o2-04, Drive Model Selection.