EasyManua.ls Logo

YASKAWA A1000 Series

YASKAWA A1000 Series
358 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
H1 Multi-Function Digital Input Selections
H1-oo Setting
Function LCD Display Description Page
20 to 2F External fault
20: NO/Always Det,
Ramp to Stop
21: NC/Always Det,
Ramp to Stop
22: NO/During
RUN, Ramp to Stop
23: NC/During
RUN, ramp to stop
24: NO/ Always Det,
Coast to Stop
25: NC/Always Det,
Coast to Stop
26: NO/During
RUN, Coast to Stop
27: NC/During
RUN, Coast to Stop
28: NO/Always Det,
Fast-Stop
29: NC/Always Det,
Fast-Stop
2A: NO/During
RUN, Fast-Stop
2B: NC/During
RUN, Fast- Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During
RUN, Alarm Only
2F: NC/During
RUN, Alarm Only
20: N.O., Always detected, ramp to stop
21: N.C., Always detected, ramp to stop
22: N.O., During run, ramp to stop
23: N.C., During run, ramp to stop
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
28: N.O., Always detected, Fast Stop
29: N.C., Always detected, Fast Stop
2A: N.O., During run, Fast Stop
2B: N.C., During run, Fast Stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
30 PID integral reset PID Intgrl Reset Closed: Resets the PID control integral value.
31 PID integral hold PID Intgrl Hold
Open: Performs integral operation.
Closed: Maintains the current PID control integral value.
32
Multi-Step Speed
Reference 4
Multi-Step Ref 4
Used in combination with input terminals set to Multi-Step Speed
Reference 1, 2, and 3. Use parameters d1-09 to d1-16 to set reference
values.
34 PID soft starter cancel PID SFS Cancel
Open: PID soft starter is enabled.
Closed: Disables the PID soft starter b5-17.
35
PID input level
selection
PID Input Invert Closed: Inverts the PID input signal.
40
Forward run command
(2-Wire sequence)
FwdRun 2Wire Seq
Open: Stop
Closed: Forward run
Note: Cannot be set together with settings 42 or 43.
41
Reverse run command
(2-Wire sequence)
RevRun 2WireSeq
Open: Stop
Closed: Reverse run
Note: Cannot be set together with settings 42 or 43.
42
Run command
(2-Wire sequence 2)
Run/Stp 2WireSeq
Open: Stop
Closed: Run
Note: Cannot be set together with settings 40 or 41.
43
FWD/REV command
(2-Wire sequence 2)
FWD/REV
2WireSeq
Open: Forward
Closed: Reverse
Note: Determines motor direction, but does not issue a Run
command. Cannot be set together with settings 40 or 41.
44 Offset frequency 1 Offset Freq 1 Closed: Adds d7-01 to the frequency reference.
45 Offset frequency 2 Offset Freq 2 Closed: Adds d7-02 to the frequency reference.
46 Offset frequency 3 Offset Freq 3 Closed: Adds d7-03 to the frequency reference.
47 Node setup CanOpenNID Setup Closed: Node setup for SI-S3 enabled.
60
DC Injection Braking
command
DCInj Activate Closed: Triggers DC Injection Braking.
61
External Speed Search
command 1
Speed Search 1
Closed: Activates Current Detection Speed Search from the maximum
output frequency (E1-04).
B.7 H Parameters: Multi-Function Terminals
290
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide

Table of Contents

Other manuals for YASKAWA A1000 Series

Related product manuals