Drive Model Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
2A0312
R/L1, S/L2, T/L3 4/0 × 2P 3/0 to 300
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 3/0 × 2P 3/0 to 300
, 1
3/0 to 300
3
3/0 to 300 M10
18 to 23
(159 to 204)
2 2 to 300 M12
32 to 40
(283 to 354)
2A0360
R/L1, S/L2, T/L3 250 × 2P 4/0 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 4/0 × 2P 4/0 to 600
, 1
250 to 600
3
3/0 to 600 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
2A0415
R/L1, S/L2, T/L3 350 × 2P 250 to 600
M12
32 to 40
(283 to 354)
U/T1, V/T2, W/T3 300 × 2P 300 to 600
, 1
300 to 600
3
3/0 to 600 M10
18 to 23
(159 to 204)
1 1 to 350 M12
32 to 40
(283 to 354)
<1> Install a GFCI when using this wire gauge in accordance with IEC/EN 61800-5-1.
<2>
Install a GFCI, or use 10 mm
2
(AWG 8) copper wire when using this wire gauge in accordance with IEC/EN 61800-5-1.
Note: When connecting peripheral devices or options to terminals , 1, 3, B1, and B2, refer to the instruction manual for each device. For
more information, contact Yaskawa or your nearest sales representative.
n
Three-Phase 400 V Class
Table 3.4
Wire Gauge and Torque Specifications (Three-Phase 400 V Class)
Drive Model Terminal
Recomm. Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Screw
Size
Tightening Torque
N·m (lb.in.)
4A0002
4A0004
R/L1, S/L2, T/L3 14 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
, 1, 2
14 to 10
B1, B2 14 to 10
12
<1>
14 to 12
4A0005
4A0007
4A0009
R/L1, S/L2, T/L3 14 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
, 1, 2
14 to 10
B1, B2 14 to 10
10
<1>
14 to 10
4A0011
R/L1, S/L2, T/L3 12 14 to 10
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2, W/T3 14 14 to 10
, 1, 2
14 to 10
B1, B2 14 to 10
10
<1>
14 to 10
4A0018
R/L1, S/L2, T/L3 10 12 to 6
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2, W/T3 10 12 to 6
, 1, 2
12 to 6
B1, B2 12 to 10
10
<1>
14 to 10 M5
2.0 to 2.5
(17.7 to 22.1)
3.6 Main Circuit Wiring
YASKAWA ELECTRIC TOEP C710616 41G YASKAWA AC Drive - A1000 Quick Start Guide
97
3
Electrical Installation

Table of Contents

Other manuals for YASKAWA A1000 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA A1000 Series and is the answer not in the manual?

YASKAWA A1000 Series Specifications

General IconGeneral
SeriesA1000
TypeAC Drive
AltitudeUp to 1000m without derating
Output Frequency0-400 Hz
Control MethodV/f Control
Overload Capacity150% for 60 seconds
Communication OptionsModbus, DeviceNet, Profibus, Ethernet/IP
Ambient Temperature-10 to 50°C
Storage Temperature-20 to 60°C
Humidity5% to 95% (non-condensing)
Enclosure RatingIP20
Horsepower0.5 to 1000 HP
Power Range0.4 - 630 kW (varies by voltage and model)
Protection FeaturesOvercurrent, Overvoltage, Undervoltage, Overheat
Cooling MethodFan Cooled
SafetySafe Torque Off (STO)