3.10 Crane Application Setup Procedure
212 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Note:
Consider the target frequency reference as the maximum output frequency. The limit start level and the hold level are calculated
differently when motoring and during regeneration.
Set the value of S4-10 × η
2
(0.9
2
= 0.81) to S4-12 as a target value. If there is no problem with the default setting of 100%, then there is
no need to change S4-12, because it will not get any higher than the target frequency.
Separate calculations are used when motoring and during regeneration. As a result, the speed is not the same when hoisting the load
and when lowering it.
Multi-Funciton Digital Input
H1-xx Setting Name Description
36 Light-load Accel 2 Enabled
ON: Enabled
OFF: Disabled
Table 3.19 Requirement for Enabling Light-load Acceleration
MFDI Function Settings S4-01 Setting Light-load Accel 2 Enable/Disable
H1-xx = 36 Digital Inputs
OFF
Unrelated to settings
The output frequency will not exceed S4-08.
ON
Light-load Acceleration 2 is enabled.
H1-xx 36
1: Light-load Accel Ctrl 1 enabled Light-load Acceleration 1 is enabled.
2: Light-load Accel Ctrl 2 enabled Light-load Acceleration 2 is enabled.
0: Light-load Accel Ctrl disabled Light-load Acceleration 1 and 2 are disabled. Uses the frequency
reference to run the motor.
Description of Operation
The following is an example of drive operation while motoring.
S4-08 - Light-load 2 Activation Freq
S4-09 - L-L 2 Motoring Limit Start Level
S4-10 - L-L 2 Motoring Hold Level
Note:
The dotted line indicates where the drive output still has headroom. Speed loss (stalling) will actually occur if the drive has insufficient
power.