11.3 b: Application
b parameters set these functions.
• Frequency reference source/Run command source
• Stopping method settings
• DC Injection Braking
• Droop Control
• Zero Servo Control
◆ b1: Operation Mode Selection
b1 parameters set the operation mode for the drive.
■ b1-01: Frequency Reference Selection 1
No.
(Hex.)
Name Description
Default
(Range)
b1-01
(0180)
Frequency Reference
Selection 1
Sets the input method for the frequency reference.
0
(0 - 3)
Note:
• The RUN light on the keypad will flash if the Run command is entered when the frequency reference is 0 Hz or below the value set in
E1-09 [Minimum Output Frequency]. Examine the setting for the frequency reference input and enter a value more than or equal to the
E1-09 value.
0 : Keypad
Use the keypad to enter the frequency reference.
The frequency reference can be changed by using and on the keypad.
1 : Digital Input
Use the MFAI terminals A1, A2, and A3 to input an analog frequency reference with a voltage or current input
signal.
• Voltage Input
Refer to this table to use a voltage signal input to one of the MFAI terminals.
Table 11.9 Frequency Reference Voltage Input
Terminal
Terminal Signal
Level
Parameter Settings
Note
Signal Level
Selection
Function Selection Gain Bias
A1 0 - 10 V H3-01 = 0 H3-02 = 0
[Frequency Reference]
H3-03 H3-04
-
-10 - 10 V H3-01 = 1
A2 0 - 10 V H3-09 = 0 H3-10 = 0
[Frequency Reference]
H3-11 H3-12 Set DIP switch S1 to “V” for
voltage input.
-10 - 10 V H3-09 = 1
A3 0 - 10 V H3-05 = 0 H3-06 = 0
[Frequency Reference]
H3-07 H3-08 Set DIP switch S4 to “AI” for
analog input.
-10 - 10 V H3-05 = 1
Figure 11.7 Example of Setting the Frequency Reference with a Voltage Signal to Terminal A1