EasyManuals Logo

YASKAWA CR700 Technical Manual

YASKAWA CR700
886 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #304 background imageLoading...
Page #304 background image
5.3 MEMOBUS/Modbus Communications
304 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Figure 5.4 Wiring Diagram for More than One Drive
Note:
Set DIP switch S2 to the ON position on the last drive of the MEMOBUS/Modbus communication network to enable the termination
resistor.
Drive Operations by MEMOBUS/Modbus
The drive parameters apply to the settings even if the drive is run during MEMOBUS/Modbus communications.
This section describes the types of usable functions and their related parameters.
Executable Function
A PLC can perform the following operations with MEMOBUS/Modbus communications at any time regardless of
parameter settings (except for H5-xx).
Observe the drive status and operate the drive from a PLC
Set and view parameters
Fault Reset Procedure
Multi-function input setting (The input command from MEMOBUS/Modbus communications and MFDI
terminals (S1 to S10) are linked by a logical OR operation.)
Drive Control
Select the external command for setting the frequency references and the motor run/stop using MEMOBUS/
Modbus communications, and set the parameters according to the application using the following table.
Table 5.2 Required Parameter Setting for Drive Control from MEMOBUS/Modbus
LOCAL Control Selected No. Name Setting Value
External reference 1
b1-01 Frequency Reference Selection 1 2 [Memobus/Modbus Communications]
b1-02 Run Command Selection 1 2 [Memobus/Modbus Communications]
External reference 2
b1-15 Frequency Reference Selection 2 2 [Memobus/Modbus Communications]
b1-16 Run Command Selection 2 2 [Memobus/Modbus Communications]
For more information about operation mode selection, refer to b1-01 [Frequency Reference Selection 1] and b1-02
[Run Command Selection 1]. Refer to H1-xx = 2 [MFDI Function Selection = External Reference 1/2 Selection]
for more information about external command.
Communications Timing
To prevent overrun of the slave side, the master cannot send a message to the same drive for a certain amount of
time. Similarly, to prevent overrun of the master side, the slave cannot send a response message to the master for a
certain amount of time. This section explains the message send/receive timing.
Command Message from Master to Slave
To prevent data loss and overrun, after the master receives a message from the slave, the master cannot send the
same type of command message to the same slave for a certain amount of time. The minimum wait time differs
depending on the type of message. Check by referencing the following table.

Table of Contents

Other manuals for YASKAWA CR700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CR700 and is the answer not in the manual?

YASKAWA CR700 Specifications

General IconGeneral
BrandYASKAWA
ModelCR700
CategoryDC Drives
LanguageEnglish

Related product manuals