10.8 E: Motor Parameters
484 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
No.
(Hex.)
Name Description
Default
(Range)
Ref.
E2-10
(0317)
Motor Iron Loss
Sets the motor iron loss.
Determined by o2-04
(0 - 65535 W)
643
E2-11
(0318)
Motor Rated Power
Sets the motor rated power in 0.01 kW increments. (1 HP = 0.746 kW)
Determined by o2-04
(0.00 - 650.00 kW)
643
E3: V/f Pattern for Motor 2
No.
(Hex.)
Name Description
Default
(Range)
Ref.
E3-01
(0319)
Motor 2 Control Mode
Selection
Sets the control method for motor 2.
Note:
When you change this setting, the drive will set all parameters that are dependent on
E3-01 to their default settings.
0 : Open Loop V/f Control
1 : V/f Control with Encoder
2 : Open Loop Vector
3 : Closed Loop Vector
2
(0 - 3)
644
E3-04
(031A)
Motor 2 Maximum
Output Frequency
Set the maximum output frequency for the motor 2 V/f pattern.
Determined by E3-01
(40.0 - 590.0 Hz)
644
E3-05
(031B)
Motor 2 Maximum
Output Voltage
Sets the maximum output voltage for the motor 2 V/f pattern.
Determined by E3-01
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)
644
E3-06
(031C)
Motor 2 Base Frequency
Sets the base frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
645
E3-07
(031D)
Motor 2 Mid Point A
Frequency
Sets a middle output frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
645
E3-08
(031E)
Motor 2 Mid Point A
Voltage
Sets a middle output voltage for the motor 2 V/f pattern.
Determined by E3-01
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)
645
E3-09
(031F)
Motor 2 Minimum
Output Frequency
Sets the minimum output frequency for the motor 2 V/f pattern.
Determined by E3-01
(0.0 - E3-04)
645
E3-10
(0320)
Motor 2 Minimum
Output Voltage
Sets the minimum output voltage for the motor 2 V/f pattern.
Determined by E3-01
(200 V Class: 0.0 - 255.0
V,
400 V Class: 0.0 - 510.0
V)
645
E3-11
(0345)
Expert
Motor 2 Mid Point B
Frequency
Sets a middle output frequency for the motor 2 V/f pattern. Set this parameter to adjust
the V/f pattern for the constant output range. Usually it is not necessary to change this
parameter.
0.0 Hz
(0.0 - E3-04)
645
E3-12
(0346)
Expert
Motor 2 Mid Point B
Voltage
Sets a middle output voltage for the motor 2 V/f pattern. Set this parameter to adjust the
V/f pattern for the constant output range. Usually it is not necessary to change this
parameter.
0.0 V
(200 V Class: 0.0 to
255.0 V, 400 V Class:
0.0 to 510.0 V)
645
E3-13
(0347)
Expert
Motor 2 Base Voltage
Sets the base voltage for the motor 2 V/f pattern. Set this parameter to adjust the V/f
pattern for the constant output range. Usually it is not necessary to change this
parameter.
0.0 V
(200 V Class: 0.0 to
255.0 V, 400 V Class:
0.0 to 510.0 V)
646
E3-14
(114E)
M2 Middle Out Freq
Volt Select
Sets the mid point A voltage for motor 2 reverse run used when b1-23 = 1 [Selection
REV Parameters = Enabled].
Determined by E3-01
and E1-03
(200 V Class: 0.0 to
255.0 V, 400 V Class:
0.0 to 510.0 V)
646
E3-15
(114F)
M2 Minimum Out Freq
Volt Select
Sets the minimum output voltage for motor 2 reverse run used when b1-23 = 1
[Selection REV Parameters = Enabled].
Determined by E3-01
and E1-03
(200 V Class: 0.0 to
255.0 V, 400 V Class:
0.0 to 510.0 V)
646
E3-20
(0BF4)
UL Motor2 Sel
Sets the motor characteristics.
0 : Constant Torque
1 : Variable Torque
2 : Auto Distinction
2
(0 - 2)
646
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV

Table of Contents