3.10 Crane Application Setup Procedure
214 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
■ S5-01/S5-04 Settings
Setting
Value
Detection Conditions
Type Operation after Detection Drive Recovery
Enabled Disabled
During
Run
During
Speed
Agree
ment
0 - x - - - - -
1 x - - x
Alarm
Acceleration prohibited
When the Run command is OFF and
the motor has stopped, the drive will
return to the state before the fault was
triggered.
*1
2 x - x -
3 x - - x
Ramps to stop according to C1-09
[Fast Stop Time]
When the Run command is OFF and
the motor has stopped, the drive will
return to the state before the fault was
triggered.
*1
4 x - x -
5 x - - x
Fault
(Triggers a fault relay
output)
Coast to Stop
Push on the keypad or turn ON
the terminal set for “Fault Reset” to
reset the fault.
6 x - x -
*1 Pushing on the keypad will not reset an alarm.
■ Multi-Function Digital Output
The following table shows the ON/OFF conditions of the MFDO terminals.
H2-xx
Setting Value
Name Description
22 Overload Detection (N.O.)
If the drive detects overload based on the conditions set for Overload Detection 1 or 2, then this
digital output will switch ON.
The digital output will switch OFF when oL5 is cleared from the keypad display.
23 Weight Det N.C.
If the drive detects overload based on the conditions set for Overload Detection 1 or 2, then this
digital output will switch OFF.
The digital output will switch ON when oL5 is cleared from the keypad display.
◆ Overtorque Detection
This function limits drive operation depending on how high the drive torque reference or the output current is in
order to provide mechanical protection to the crane. If the drive detects an overtorque situation, then it displays
oL3 [Overtorque Detection 1] or oL4 [Overtorque Detection 2] on the keypad. You can set 2 levels for overtorque
detection, and 2 types of action to take after detecting overtorque.
Note:
The overtorque detection function is disabled when the Run command source is set to the keypad.
■ Related Parameters
Table 3.21 Overtorque Detection Parameters
No. Name Description Error Code
S6-01 OverT Detect Operation Select 1
Enables overtorque detection, and sets the conditions for detection as well as the operation to
perform after an overtorque is detected.
oL3
S6-04 OverT Detect Operation Select 2 oL4
S6-02 Overtorque Detection Level 1
Sets the level to trigger an overtorque.
• V/f Control Mode
Sets the amount of torque that triggers overtorque detection as the motor rated current is 100%.
• OLV Control
Sets the amount of torque that triggers overtorque detection as the motor rated torque is 100%.
-
S6-05 Overtorque Detection Level 2 -
S6-03 Overtorque Detection Time 1
If the motor current and motor torque exceed the value set in S6-02 for longer than the time set in
this parameter, then Overtorque 1 will be detected.
oL3
S6-06 Overtorque Detection Time 2
If the motor current and motor torque exceed the value set in S6-05 for longer than the time set in
this parameter, then Overtorque 2 will be detected.
oL4
S6-09 Torque Detection Filter Time
Sets the time constant for a primary filter to the torque reference or to the output current used to
detect overtorque.
-