Parameter List
10
10.4 A: Initialization Parameters
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 469
10.4 A: Initialization Parameters
A1: Initialization
No.
(Hex.)
Name Description
Default
(Range)
Ref.
A1-00
(0100)
RUN
Language Selection
Sets the language for the LCD keypad.
Note:
When you use A1-03 [Initialize Parameters] to initialize the drive, the drive will
not reset this parameter.
0 : English
1 : Japanese
7 : Chinese
0
(0, 1, 7)
569
A1-01
(0101)
RUN
Access Level Selection
Sets user access to parameters. The access level controls the parameters shown on the
keypad and which parameters you can set.
0 : Operation Only
1 : User Parameter
2 : Advanced Level
3 : Expert Level
2
(0 - 3)
569
A1-02
(0102)
Control Method
Selection
Sets the control method for the drive application and the motor.
0 : V/f Control
1 : V/f Control with Encoder
2 : Open Loop Vector
3 : Closed Loop Vector
4 : Advanced Open Loop Vector
2
(0 - 4)
570
A1-03
(0103)
Initialize Parameters
Sets parameters to default values.
0 : No Initialization
1110 : User Initialization
2220 : 2-Wire Initialization
0
(0 - 2220)
570
A1-04
(0104)
Password
Enter the correct password set in A1-05 [Password Setting] to unlock parameters. You
can view parameter settings. Monitors are locked Enter the password in A1-04
[Password] to unlock and change the settings.
0000
(0000 - 9999)
571
A1-05
(0105)
Password Setting
Set the password to lock parameters and prevent changes to parameter settings. The
following parameters can be changed when the user enters the correct password in A1-
04 [Password] that matches the password set in A1-05.
0000
(0000 - 9999)
572
A1-06
(0127)
Application Preset
Sets the drive to operate in selected application conditions.
0 : General-purpose
1 : Crane (Hoist)
2 : Crane (Traveling)
3 : Closed Loop Crane (Hoist)
0
(0 - 3)
572
A1-11
(111D)
Expert
Firmware Update Lock
Protects the drive firmware. When you enable the protection, you cannot update the
drive firmware.
0 : Disabled
1 : Enabled
0
(0, 1)
582
A1-12
(1564)
Bluetooth ID
Sets the password necessary to use Bluetooth to control the drive with a smartphone or
tablet.
1915
(0000 - 9999)
582
A1-13
(156F)
All Function Parameter
Display
Shows and hides applicable parameters.
0 : Disabled
1 : Enabled
1
(0, 1)
582
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV

Table of Contents