Parameter Details
11
11.8 H: Terminal Functions
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 711
H2-69: Digital Output4 Secondary Func
No.
(Hex.)
Name Description
Default
(Range)
H2-69
(1B4F)
Expert
Digital Output4 Secondary
Func
Sets the second function for terminal P1-C1. Outputs the logical calculation results of the
terminals assigned to functions by H2-04 [Terminal P2-C2 Function Select].
F
(0 - FF)
H2-70: DigitalOutput4 Logical Operation
No.
(Hex.)
Name Description
Default
(Range)
H2-70
(11F9)
Expert
DigitalOutput4 Logical
Operation
Sets the logical operation for the functions set in H2-04 [Terminal P1-C1 Function Select] and
H2-69 [Digital Output4 Secondary Func].
0
(0 - 8)
Note:
Refer to
Output of Logical Operation Results of MFDO on page 703 for more information about the relationship between parameter
settings and logical operations.
H2-71: Digital Output 4 Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-71
(11FA)
Expert
Digital Output 4 Delay
Time
Sets the minimum on time used to output the logical calculation results from terminal P1-C1.
0.1 s
(0.0 - 25.0 s)
H2-72: Digital Output 5 Secondary Func
No.
(Hex.)
Name Description
Default
(Range)
H2-72
(11FB)
Expert
Digital Output 5 Secondary
Func
Sets the second function for terminal P2-C2. The logical calculation results of the terminals
assigned to functions by H2-05 [Term P2-C2 Function Selection] is output.
F
(0 - FF)
H2-73: DigitalOutput5 Logical Operation
No.
(Hex.)
Name Description
Default
(Range)
H2-73
(11FC)
Expert
DigitalOutput5 Logical
Operation
Sets the logical operation for the functions set in H2-05 [Term P2-C2 Function Selection] and H2-
72 [Digital Output 5 Secondary Func].
0
(0 - 8)
H2-74: Digital Output 5 Delay Time
No.
(Hex.)
Name Description
Default
(Range)
H2-74
(11FD)
Expert
Digital Output 5 Delay
Time
Sets the minimum ON time used to output the logical calculation results from terminal P2-C2.
0.1 s
(0.0 - 25.0 s)
MFDO Setting Values
Selects the function configured to MFDO.
0: During Run
Setting Value Function Description
0 During Run
The terminal activates when you input a Run command and when the drive is outputting voltage.
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV

Table of Contents

Other manuals for YASKAWA CR700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CR700 and is the answer not in the manual?

YASKAWA CR700 Specifications

General IconGeneral
BrandYASKAWA
ModelCR700
CategoryDC Drives
LanguageEnglish

Related product manuals