Parameter List
10
10.10 H: Terminal Functions
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 509
Setting Value Function Description Ref.
62 Modbus Reg 1 Status
Satisfied
The terminal activates when the bit specified by H2-08 [Modbus Register 1 Bit Select] for the MEMOBUS register
address set with H2-07 [Modbus Register 1 Address Select] activates.
722
63 Modbus Reg 2 Status
Satisfied
The terminal activates when the bit specified by H2-10 [Modbus Register 2 Bit Select] for the MEMOBUS register
address set with H2-09 [Modbus Register 2 Address Select] activates.
722
66 Comparator1
The terminal activates if the monitor value set with H2-20 [Comparator 1 Monitor Selection] is in range of the
values of H2-21 [Comparator 1 Lower Limit] and H2-22 [Comparator 1 Upper Limit] for the time set in H2-24
[Comparator 1 On-Delay Time].
722
67 Comparator2
The terminal activates if the monitor value set with H2-26 [Comparator 2 Monitor Selection] is not in the range of
the values of H2-27 [Comparator 2 Lower Limit] and H2-28 [Comparator 2 Upper Limit] for the time set in H2-
30 [Comparator 2 On-Delay Time].
722
69 External Power 24V
Supply
The terminal activates when there is an external 24V power supply between terminals PS-AC.
ON : The external 24V power supply is supplying power.
OFF : The external 24V power supply is not supplying power.
723
6A Data Logger Error
The terminal activates when the drive detects a LoG [Com Error / Abnormal SD card].
723
B1 DC Injection Braking at
Start
The terminal activates when the motor is started and during DC Injection Braking.
723
B2 DC Injection Braking at
Stop
The terminal activates when the motor is stopped and during DC Injection Braking.
723
B3 Motor 3 Selection
The terminal activates when you select motor 3.
ON : Motor 3 Selected
OFF : Motor 1 or Motor 2 Selected
723
216
226
100 - 1FF Inverse Output of 0 to
FF
Causes inverse output of the function for the selected MFDO. Uses the last two digits of 1xx to select which
function to inversely output.
723
H3: Analog Inputs
No.
(Hex.)
Name Description
Default
(Range)
Ref.
H3-01
(0410)
Terminal A1 Signal
Level Select
Sets the input signal level for MFAI terminal A1.
0 : 0-10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
0
(0, 1)
725
H3-02
(0434)
Terminal A1 Function
Selection
Sets the function for MFAI terminal A1.
0
(0 - FF)
726
H3-03
(0411)
RUN
Terminal A1 Gain
Setting
Sets the gain of the analog signal input to MFAI terminal A1.
100.0%
(-999.9 - +999.9%)
726
H3-04
(0412)
RUN
Terminal A1 Bias
Setting
Sets the bias of the analog signal input to MFAI terminal A1.
0.0%
(-999.9 - +999.9%)
726
H3-05
(0413)
Terminal A3 Signal
Level Select
Sets the input signal level for MFAI terminal A3.
0 : 0-10V (Lower Limit at 0)
1 : -10 to +10V (Bipolar Reference)
0
(0, 1)
726
H3-06
(0414)
Terminal A3 Function
Selection
Sets the function for MFAI terminal A3.
2
(0 - FF)
726
H3-07
(0415)
RUN
Terminal A3 Gain
Setting
Sets the gain of the analog signal input to MFAI terminal A3.
100.0%
(-999.9 - +999.9%)
727
H3-08
(0416)
RUN
Terminal A3 Bias
Setting
Sets the bias of the analog signal input to MFAI terminal A3.
0.0%
(-999.9 - +999.9%)
727
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV