Parameter List
10
10.9 F: Options
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 487
10.9 F: Options
F1: Encoder Option Setup
No.
(Hex.)
Name Description
Default
(Range)
Ref.
F1-01
(0380)
Encoder 1 Pulse Count
(PPR)
Sets the number of output pulses per revolution of the encoder.
1024
(1 - 60000 ppr)
651
F1-02
(0381)
Encoder Signal Loss
Detect Sel
Sets the motor operation when PGo [Encoder (PG) Feedback Loss] is detected.
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
4 : No Alarm Display
1
(0 - 4)
652
F1-03
(0382)
Overspeed Detection
Selection
Selects the motor operation when the drive detects oS [Overspeed].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
1
(0 - 3)
652
F1-04
(0383)
Speed Deviation
Detection Select
Selects the motor operation when the drive detects dEv [Speed Deviation].
0 : Ramp to Stop
1 : Coast to Stop
2 : Fast Stop (Use C1-09)
3 : Alarm Only
3
(0 - 3)
652
F1-05
(0384)
Encoder 1 Rotation
Selection
Sets the output sequence for the A and B pulses from the encoder, assuming that the
motor is operating in the forward direction.
0 : Pulse A leads in FWD Direction
1 : Pulse B leads in FWD Direction
Determined by A1-02
(0, 1)
653
F1-06
(0385)
Encoder 1 Pulse Monitor
Scaling
Sets the ratio between the pulse input and the pulse output of the encoder as a 3-digit
number. The first digit is the numerator and the second and third digits set the
denominator.
The dividing ratio = (1 + x)/yz when the setting value is a 3-digit value (xyz).
001
(001 - 032, 102 - 132 (1 -
1/32))
653
F1-08
(0387)
Overspeed Detection
Level
Sets the detection level of oS [Overspeed] as a percentage when the maximum output
frequency is 100%.
115%
(0 - 120%)
653
F1-09
(0388)
Overspeed Detection
Delay Time
Sets the length of time that the speed feedback must be more than the F1-08 level to
cause oS [Overspeed].
Note:
If A1-02 = 0 [Control Method Selection = V/f], you must set H6-01 = 3 [Terminal
RP Pulse Train Function = Speed Feedback (V/F Control)] to enable this
parameter.
Determined by A1-02
(0.0 - 2.0 s)
653
F1-10
(0389)
Speed Deviation
Detection Level
Sets the detection level of dEv [Speed Deviation] as a percentage when the maximum
output frequency is 100%.
10%
(0 - 50%)
654
F1-11
(038A)
Speed Deviation Detect
DelayTime
Sets the length of time that the difference between the frequency reference and speed
feedback must be more than the level in F1-10 to cause dEv [Speed Deviation].
Note:
If A1-02 = 0 [Control Method Selection = V/f], you must set H6-01 = 3 [Terminal
RP Pulse Train Function = Speed Feedback (V/F Control)] to enable this
parameter.
0.5 s
(0.0 - 10.0 s)
654
F1-12
(038B)
Encoder 1 Gear Teeth 1
Sets the number of gear teeth on the motor side. This parameter and F1-13 [Encoder 1
Gear Teeth 2] set the gear ratio between the motor and encoder.
0
(0 - 1000)
654
F1-13
(038C)
Encoder 2 Gear Teeth 1
Sets the number of gear teeth on the load side. This parameter and F1-12 [Encoder 1
Gear Teeth 1] set the gear ratio between the motor and encoder.
0
(0 - 1000)
654
F1-14
(038D)
Encoder Open-Circuit
Detect Time
Sets the detection time for PGo [Encoder (PG) Feedback Loss].
Note:
Motor speed and load conditions can cause ov [Overvoltage] and oC [Overcurrent]
faults.
2.0 s
(0.0 - 10.0 s)
654
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV

Table of Contents

Other manuals for YASKAWA CR700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CR700 and is the answer not in the manual?

YASKAWA CR700 Specifications

General IconGeneral
ModelCR700
CategoryDC Drives
Protection ClassIP20
Output Power0.5 to 300 HP
Horsepower Range0.5 - 300 HP
Communication InterfaceRS-485
Protection FeaturesOvercurrent, Overvoltage, Short Circuit