Parameter List
10
10.5 b: Application
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 471
10.5 b: Application
b1: Operation Mode Selection
No.
(Hex.)
Name Description
Default
(Range)
Ref.
b1-01
(0180)
Frequency Reference
Selection 1
Sets the input method for the frequency reference.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
0
(0 - 3)
584
b1-02
(0181)
Run Command Selection
1
Sets the input method for the Run command.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
1
(0 - 3)
585
b1-03
(0182)
Stopping Method
Selection
Sets the method to stop the motor after removing a Run command or entering a Stop
command.
Note:
When A1-02 = 3, 4 [Control Method Selection = CLV, AOLV], the setting range is
0, 1, 3.
0 : Ramp to Stop
1 : Coast to Stop
2 : DC Injection Braking to Stop
3 : Coast to Stop with Timer
0
(0 - 3)
586
b1-04
(0183)
Reverse Operation
Selection
Sets the reverse operation function.
0 : Reverse Enabled
1 : Reverse Disabled
0
(0, 1)
588
b1-05
(0184)
Operation Below
Minimum Freq
Sets the operation to perform when the frequency reference falls below the value set in
E1-09 [Minimum Output Frequency].
0 : Operate at Frequency Reference
1 : Coast to Stop
2 : Operate at Minimum Frequency
3 : Operate at Zero Speed
0
(0 - 3)
589
b1-06
(0185)
Digital Input Reading
Sets the number of times that the drive reads the sequence input command to prevent
malfunction because of electrical interference.
0 : Single Scan
1 : Double Scan
1
(0, 1)
590
b1-14
(01C3)
Phase Order Selection
Sets the phase order for output terminals U/T1, V/T2, and W/T3. This parameter can
align the Forward Run command from the drive and the forward direction of the motor
without changing wiring.
0 : Standard
1 : Switch Phase Order
0
(0, 1)
590
b1-15
(01C4)
Frequency Reference
Selection 2
Sets the input method for frequency reference 2.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
0
(0 - 3)
590
b1-16
(01C5)
Run Command Selection
2
Sets the input method for Run Command 2 when the user switches the control circuit
terminals ON/OFF to change the Run command source.
0 : Keypad
1 : Analog Input
2 : Memobus/Modbus Communications
3 : Option PCB
0
(0 - 3)
592
b1-17
(01C6)
Run Command at Power
Up
Sets drive response when the CPU changes from de-energized to energized and there is
an active Run command. Set this parameter in applications where energizing or de-
energizing the drive enables the Run command.
0 : Disregard Existing RUN Command
1 : Accept Existing RUN Command
0
(0, 1)
592
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV
V/f
CL-V/f
OLV
CLV
AOLV