Parameter Details
11
11.9 L: Protection Function
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 745
11.9 L: Protection Function
L parameters set the following functions.
Motor Overload Protection
Operation During Momentary Power Loss
Stall Prevention
Speed Detection
Torque Limit
Hardware Protection
L1: Motor Protection
L1 parameters set the motor overload protection function.
Motor Protection Using Positive Temperature Coefficient (PTC) Thermistors
The temperature resistance characteristics of three PTC thermistors in the motor stator winding protect the motor
from overheat.
The PTC thermistors must have the characteristics in motor 1 phase as shown in the following graph.
Figure 11.85 PTC Thermistor Temperature and Resistance
When the PTC input signal input to the drive is more than the overload alarm level, the drive detects oH3 [Motor
Overheat (PTC Input)]. The drive continues the operation set in L1-03 [Motor Thermistor oH Alarm Select].
The overheat fault level triggers an oH4 [Motor Overheat Fault (PTC Input)] fault, and outputs a fault signal. The
drive outputs a fault signal, and stops the motor with the stop method set in L1-04 [Motor Thermistor oH Fault
Select].
Note:
PTC is an acronym for Positive Temperature Coefficient.
The following figure shows the setting procedure when you use terminal A3.
1. Connect the PTC thermistor input from the motor to analog input terminal A3 on the drive.
Figure 11.86 Connect Motor PTC
2. Set drive DIP Switch S4 to PTC.