11.8 H: Terminal Functions
734 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Figure 11.79 Torque Limits from Parameters and Analog Inputs
■ 11: Reverse Torque Limit
Setting Value Function Description
11 Reverse Torque Limit
Enters the load torque limit if the motor rated torque is 100%.
Note:
When you use L7-01 to L7-04 and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
■ 12: Regenerative Torque Limit
Setting Value Function Description
12 Regenerative Torque Limit
Enters the regenerative torque limit if the motor rated torque is 100%.
Note:
When you use L7-01 to L7-04 and analog inputs to set torque limits for the same quadrant, it will enable the lower torque limit.
■ 14: Torque Compensation
Setting Value Function Description
14 Torque Compensation
Enters the torque compensation value if the motor rated torque is 100%.
■ 15: General Torque Limit
Setting Value Function Description
15 General Torque Limit
Enters the torque limit that is the same for all quadrants for forward, reverse, and regenerative operation if the motor rated
torque is 100%.
■ 1F: Not Used
Setting Value Function Description
1F Not Used
Use this setting for unused terminals or to use terminals in through mode.
When you set a terminal that you do not use to 1F, you can use the signal that is input to that terminal as the PLC
analog signal input from MEMOBUS/Modbus communications or the communication option. This input signal
does not have an effect on drive operation. This signal functions the same as F (Through Mode).
◆ H4: Analog Outputs
H4 parameters set the drive analog monitors. These parameters select monitor parameters, adjust gain and bias,
and select output signal levels.