Specifications
9
9.3 Model Specifications (400 V Class)
YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual 431
9.3 Model Specifications (400 V Class)
Table 9.3 Rating (400 V Class)
Model 4002 4003 4005 4006 4007 4009 4015 4018 4024 4031 4039
Maximum Applicable Motor Output
*1
(kW)
0.55 1.1 1.5 2.2 3 4.0 5.5 7.5 11 15 18.5
Input
Rated
Input
Current
*2
(A)
AC 1.9 3.5 4.7 6.7 8.9 11.7 15.8 21.2 30.6 41.3 50.5
DC 2.3 4.3 5.8 8.2 11 15 20 26 38 51 62
Output
Rated Output Capacity
*3
(kVA)
1.2 2.2 3.2 3.6 4.7 6.1 10 12 16 20 26
Rated Output Current
(A)
1.8 3.4 4.8 5.5 7.2 9.2 14.8 18 24 31 39
Overload Tolerance
150% of the rated output current for 60 s
Note:
Derating can be necessary for applications that start and stop frequently.
Carrier Frequency
8 kHz without derating the drive capacity.
Derate the drive capacity to use values to 15 kHz maximum.
Maximum Output
Voltage
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output
Frequency
AOLV (Advanced Open Loop Vector): 120 Hz
CL-V/f (Closed Loop V/f Control), CLV (Closed Loop Vector): 400 Hz
V/f (V/f Control), OLV (Open Loop Vector): 590 Hz
Measures
for
Harmonics
DC reactor External options
Braking
Device
Braking Transistor Standard internal characteristics
EMC
Filter
EMC Filter
IEC61800-3, C3
Factory option
Models 4xxxB: There is a category C3 EMC filter in the drive.
Power
Supply
Rated Voltage/Rated
Frequency
Three-phase AC power supply 380 V to 480 Vat 50/60 Hz
DC power supply 513 V to 679 V
Permitted Voltage
Fluctuation
-15% to +10%
Permitted Frequency
Fluctuation
±5%
Input Power
*4
(kVA) 1.5 2.8 3.7 5.3 7.1 9.3 13 17 24 33 40
*1 The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated
output current of the drive output amps must be equal to or more than the motor rated current.
*2 Assumes the value at the rated output current. The input current rating changes when the power supply transformer, input reactor,
wiring connections, or power supply impedance change.
*3 The rated output capacity is calculated with a rated output voltage of 380 V.
*4 The power supply capacity is calculated with the voltage between lines at 480 V.
Table 9.4 Rating (400 V Class)
Model 4045 4060 4075 4091 4112 4150 4180 4216 4260 4304 4371
Maximum Applicable Motor Output
*1
(kW)
22 30 37 45 55 75 90 110 132 160 200
Input
Rated
Input
Current
*2
(A)
AC 43.1 58.3 71.5 86.5 105 142 170 207 248 300 373
DC 53 72 88 106 129 174 209 254 304 367 457