9.3 Model Specifications (400 V Class)
432 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Model 4045 4060 4075 4091 4112 4150 4180 4216 4260 4304 4371
Output
Rated Output Capacity
*3
(kVA)
30 39 49 60 74 99 118 142 171 200 244
Rated Output Current
(A)
45 60 75 91 112 150 180 216 260 304 371
Overload Tolerance
150% of the rated output current for 60 s
Note:
Derating can be necessary for applications that start and stop frequently.
Carrier Frequency
5 kHz without derating the drive capacity.
Derate the drive capacity to use values to 10 kHz maximum.
Maximum Output
Voltage
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output
Frequency
AOLV (Advanced Open Loop Vector): 120 Hz
CL-V/f (Closed Loop V/f Control), CLV (Closed Loop Vector): 400 Hz
V/f (V/f Control), OLV (Open Loop Vector): 590 Hz
Measures
for
Harmonics
DC reactor Standard internal characteristics
Braking
Device
Braking Transistor Standard internal characteristics External options
EMC
Filter
EMC Filter
IEC61800-3, C3
Factory option
Models 4xxxB: There is a category C3 EMC filter in the drive.
Power
Supply
Rated Voltage/Rated
Frequency
Three-phase AC power supply 380 V to 480 Vat 50/60 Hz
DC power supply 513 V to 679 V
Permitted Voltage
Fluctuation
-15% to +10%
Permitted Frequency
Fluctuation
±5%
Input Power
*4
(kVA) 34 46 57 69 84 113 136 165 198 239 297
*1 The maximum applicable motor output complies with 380 V motor ratings as specified in Annex G of IEC 60947-4-1. The rated
output current of the drive output amps must be equal to or more than the motor rated current.
*2 Assumes the value at the rated output current. The input current rating changes when the power supply transformer, input reactor,
wiring connections, or power supply impedance change.
*3 The rated output capacity is calculated with a rated output voltage of 380 V.
*4 The power supply capacity is calculated with the voltage between lines at 480 V.
Table 9.5 Rating (400 V Class)
Model 4414 4453 4605
Maximum Applicable Motor Output
*1
(kW) 220 250 315
Input Rated Input Current
*2
(A)
AC 410 465 584
DC 502 569 715
Output
Rated Output Capacity
*3
(kVA) 272 298 398
Rated Output Current (A) 414 453 605
Overload Tolerance
150% of the rated output current for 60 s
Note:
Derating can be necessary for applications that start and stop frequently.
Carrier Frequency
2 kHz without derating the drive capacity.
Derate the drive capacity to use values to 5 kHz maximum.
Maximum Output Voltage
Three-phase 380 V to 480 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
AOLV (Advanced Open Loop Vector): 120 Hz
CL-V/f (Closed Loop V/f Control), CLV (Closed Loop Vector): 400 Hz
V/f (V/f Control), OLV (Open Loop Vector): 590 Hz
Measures for Harmonics DC reactor
Standard internal characteristics
Braking Device Braking Transistor External options
EMC Filter
EMC Filter
IEC61800-3, C3
Factory option
Models 4xxxB: There is a category C3 EMC filter in the drive.