9.5 Drive Derating
438 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Model
Rated Current (A)
2 kHz 5 kHz 8 kHz 10 kHz 12.5 kHz 15 kHz
4091
91.0 91.0 91.0 80.6 67.6 54.6
4112
112.0 112.0 91.8 78.4 - -
4150
150.0 150.0 123.0 105.0 - -
4180
180.0 180.0 147.6 126.0 - -
4216
216.0 216.0 177.1 151.2 - -
4260
260.0 260.0 213.2 182.0 - -
4304 304.0
304.0 249.3 212.8 - -
4371
371.0 371.0 304.2 259.7 - -
4414
389.0 324.8 - - - -
4453
453.0 378.3 - - - -
4605
605.0 505.2 - - - -
Altitude Derating
Install the drive in a location that has an altitude of 1000 m (3281 ft) or lower.
Derate the output current by 1% for each 100 m (328 ft) to install the drive in altitudes between 1000 to 4000 m
(3281 to 13123 ft).
It is not necessary to derate the rated voltage in these conditions:
Installing the drive at 2000 m (6562 ft) or lower
Installing the drive between 2000 to 4000 m (6562 to 13123 ft) and grounding the neutral point on the power
supply.
If you do not ground the drive with a neutral network, contact Yaskawa or your nearest sales representative.

Table of Contents