9.2 Model Specifications (200 V Class)
430 YASKAWA SIEPC71061723A YASKAWA AC Drive CR700 Technical Manual
Model 2088 2115 2145 2180 2215 2283 2346 2415
Output
Rated Output Capacity
*3
(kVA)
33.5 43.8 55.3 68.6 81.9 108 132 158
Rated Output Current (A) 88 115 145 180 215 283 346 415
Overload Tolerance
150% of the rated output current for 60 s
Note:
Derating can be necessary for applications that start and stop frequently.
Carrier Frequency
5 kHz without derating the drive capacity.
Derate the drive capacity to use values to 10 kHz maximum.
Maximum Output Voltage
Three-phase 200 V to 240 V
Note:
The maximum output voltage is proportional to the input voltage.
Maximum Output Frequency
• AOLV (Advanced Open Loop Vector): 120 Hz
• CL-V/f (Closed Loop V/f Control), CLV (Closed Loop Vector): 400 Hz
• V/f (V/f Control), OLV (Open Loop Vector): 590 Hz
Measures for
Harmonics
DC reactor Standard internal characteristics
Braking
Device
Braking Transistor Standard internal characteristics External options
EMC Filter
EMC Filter
IEC61800-3, C3
Factory option
• Models 2xxxB: There is a category C3 EMC filter in the drive.
Power Supply
Rated Voltage/Rated
Frequency
• Three-phase AC power supply 200 V to 240 Vat 50/60 Hz
• DC power supply 270 V to 340 V
Permitted Voltage Fluctuation
-15% to +10%
Permitted Frequency
Fluctuation
±5%
Input Power
*4
(kVA) 34.1 46.1 56.5 68.2 83.1 113 135 164
*1 The maximum applicable motor output complies with 208 V motor ratings as specified in NEC Table 430.250. The rated output
current of the drive output amps must be equal to or more than the motor rated current.
*2 Assumes the value at the rated output current. The input current rating changes when the power supply transformer, input reactor,
wiring connections, or power supply impedance change.
*3 The rated output capacity is calculated with a rated output voltage of 208 V.
*4 The power supply capacity is calculated with the voltage between lines at 240 V.